Q46C 2E Conductivity Monitor

The reliable and accurate low-level water quality measurements required for such high purity water systems

Key benefits

  • Reliable and accurate low-level conductivity measurement
  • Trace contamination detection
  • Programmable to display reading in Meg-ohm instead of microSiemens

Applications

  • Low-level conductivity measurements are essential for monitoring a variety of high purity water systems
  • Operation of deionizers, reverse osmosis membranes, ion exchange systems and heat exchangers
  • Low-level measurements for high purity water systems
Category:

Continuous water quality monitoring of conductivity

Low-level Conductivity measurements are essential for a variety of water quality monitoring. The proper operation of deionizers, reverse osmosis membranes, ion exchange systems, and heat exchangers require constant monitoring to ensure high quality production.

ATi’s Q46C2 2E Conductivity monitor provides large, easy-to-read LCD displays with a second display line for indication of temperature or other operational information. And for those applications where results in resistivity units are preferred, Q46C2 monitors can be programmed to display readings in Meg-ohm units instead of microSiemens.

Q46C2 conductivity monitors can also be configured to measure and display the concentration of chemicals used in various process applications. For applications where there are several chemicals dissolved in solution, the Q46C2 monitor can be configured to measure and display the concentration of total dissolved solids (TDS). Temperature compensation can either be made by custom compensation table or a single linear compensation factor.

Features & specification

  • Adaptable – Available in a Concentration version for direct display of chemical concentrations and for Total Dissolved Solids.
  • Customized Response with a user configurable table for a custom concentration curve.
  • Analog Output Options
  • Additional Outputs – Expansion board to add a third 4-20 mA analog output
  • AC or DC Power Options
  • PID Output – Standard PID control function assignable to one analog output.
  • Digital Communications options for Profibus-DP, Modbus-RTU, or Ethernet-IP
  • Three SPDT relays are standard, with relay functions programmable for alarm, control, or trouble indication. Three additional low power relays available as an option.
  • Flexible Mounting Large, clear Display
ELECTRONIC MONITOR
Display Range 0-2.000 / 20.00 / 200.0 / 2000 µS
Accuracy 0.1% of selected range
Repeatability 0.1% of selected range
Non-Linearity 0.1% of selected range
Temperature Drift 0.03% of span/°C
Power 100-240 VAC ±10%, 50/60 Hz, 10 VA max. 12-24 VDC, 500 mA max
Analog Outputs Two isolated 4-20 mA outputs, 900 Ω load max (3rd output optional)
Relays Three SPDT relays, rated 6 amp at 250 VAC, 5 amp at 24 VDC (3 additional low-power SPST relays optional)
Display 4-digit, 0.75″ numeric LCD with 12-character second line, LED backlight
Enclosure NEMA 4X Polycarbonate, V-0 Flammability
Operating Conditions -20 to 60°C (-4 to 140°F)
Weight 6 lbs (2.7 kg) with Sensor
Sensitivity 0.05% of span
Digital Output Profibus-DP, Modbus-RTU, or Ethernet-IP
Mounting Wall mounting kit standard, panel mount bracket and pipe u-bolts available
Size 5.6″ W x 4.9″ H x 6.4″ D
SENSOR
Sensor Type 2-Electrode
Materials Titanium; PEEK
Cable Length 15 ft (4.6 m) standard, 60 ft (18.3 m) max. with junction box
Temperature Limits 0-125°C
Pressure Limit 100 PSIG max.
Connection 1/2″ NPT or 1-1/2″ Sanitary-Style
Temperature Element Pt1000 RTD
ORDERING INFORMATION Model Q46C2-A-B-C-D-E-F 2-Electrode Monitor
Suffix A – Power
1 – 100-240 VAC, ±10%, 50/60 Hz
2 – 12-24 VDC (requires 500 mA)
Suffix B – Sensor Type
1 – 0.05 Cell, Titanium, ½” NPT Compression fitting
2 – 0.05 Cell, Titanium, ½” fitting, with connector (Requires opt. C4)
3 – 0.05 Cell, Titanium, ½” fitting, without connector (Requires opt. C4)
4 – 0.5 Cell, Titanium, ½” NPT Compression fitting
5 – 0.5 Cell, Titanium, 1-½” Sanitary fitting
6 – 0.5 Cell, 316SS, 1-½” Sanitary fitting
Suffix C – Cable Length
1 – 15′
2 – 30′
3 – Special
4 – 25 ft (7.6 m) with quick-connect plug (for sensor type B2 & B3)
Suffix D – Digital Output
1 – None
2 – Profibus-DP
3 – Modbus-RTU
4 – Ethernet-IP
Suffix E – Optional Output
0 – None
1 – One additional 4-20 mA output
2 – Three additional low power relays (SPST, 0.5 A max.)
Suffix F – Measurement Type
1 – Conductivity
2 – Concentration
ACCESSORIES
07-0100 Junction Box, NEMA 4X
31-0057 Sensor Interconnect cable
05-0094 Panel Mount Bracket
47-0005 2 “U” Bolts, 304SS
07-0121 1/2 DIN panel mount kit
51-0067 Conductivity Standard – 10 μS, Package of 100 cc bottles
09-0046 Conductivity Standard – 84 microSiemens, 500 mL
NOTES
1 – All sensor cable lengths greater than 30 feet require a Junction Box (07-0100) and Sensor Interconnect Cable (31-0057).
2 – Pipe mount requires two 2″ U-bolts (47-0005).
3 – Sensor types B2 and B3 are not for use in extremely wet environments.

Q46C 2E Conductivity Monitor

Download

Product reviews

Review Q46C 2E Conductivity Monitor

5 0% | 0 review
4 0% | 0 review
3 0% | 0 review
2 0% | 0 review
1 0% | 0 review
Review Q46C 2E Conductivity Monitor
Choose a image
0 character ( Minimum of 10)
    +

    There are no reviews yet.

    No comments yet

    Related products

    Thiết bị giám sát độ dẫn điện Q46C2 2E

    Q46C 2E Conductivity Monitor

    The reliable and accurate low-level water quality measurements required for such high purity water systems
    Find out more
    Máy đo Clo dư Q46H/62-63

    Q46H/62-63 Residual Chlorine Monitor

    Easy online monitoring and control of chlorination systems, with minimal maintenance
    Find out more
    Thiết bị giám sát Hydro Peroxide Q46/84

    Q46/84 Hydrogen Peroxide Monitor

    Offers continuous measurement of H2O2 concentrations in aqueous systems
    Find out more
    Thiết bị giám sát Axit Peracetic Q46/85

    Q46/85 Peracetic Acid Monitor

    An on-line water quality monitor capable of providing real time measurement of low levels of PAA in solution
    Find out more
    Thiết bị giám sát Sulfide Q46S/81

    Q46S/81 Dissolved Sulfide Monitor

    Provides an improved method for measuring sulfides in solution
    Find out more
    Thiết bị giám sát độ dẫn điện kiểu Toroidal Q46CT

    Q46CT Toroidal Conductivity Monitor

    Meet virtually any conductivity water quality monitoring and control application
    Find out more
    Thiết bị giám sát Ozone hòa tan trong nước Q46H/64

    Q46H/64 Dissolved Ozone Monitor

    Water quality monitoring and controlling ozone treatment systems
    Find out more
    Thiết bị giám sát quy trình rửa ngược FilterSmart

    FilterSmart Gravity Filter Backwash Monitor

    Allows water managers to monitor the backwashing process by measuring filter media level and turbidity with a single sensor
    Find out more

    Subscribe to Content

    If you need to copy the content, please leave your information, and we will respond as soon as possible. Sincerely, thank you!